Single-Zone, CO2-Based Demand-Controlled Ventilation
Clarifying the relationship between carbon-dioxide level and ventilation rate
Reducing the amount of outdoor air entering a space when an HVAC system is mechanically cooling or heating and an air-side economizer is inactive has distinct advantages. For some spaces, demand-controlled ventilation (DCV) based on changes in occupancy may be desirable. According to one method of DCV, ventilation rate is adjusted based on carbon-dioxide (CO2) level. Unfortunately, many designers do not have a clear understanding of the relationship between CO2 and ventilation and the requirements for proper ventilation control. This article will clarify the relationship between CO2 level and ventilation rate and offer suggestions for improving traditional single-setpoint CO2 DCV through the addition of a direct outdoor-airflow-measuring device.
Application of DCV
Generally, DCV should be considered only for high-occupant-density spaces with potential for significant changes in population density. Most standards and rating systems (American Society of Heating, Refrigerating and Air-Conditioning Engineers [ASHRAE]; Title 24, Part 6, of the California Code of Regulations; Leadership in Energy and Environmental Design [LEED]) consider high occupant density to be 25 or more people per 1,000 sq ft. DCV should not be considered for low-occupant-density spaces because the uncertainty of most DCV techniques is too great and the potential benefit too meager for practical application.
CO2 Level and Ventilation
Indoor CO2 level is used to estimate outdoor-airflow rate per person based on a steady-state relationship (Figure 1), which can be applied to single-zone systems.
Mass-balance equation:
(In = Out)
Co × Vo + N × P = Ci × Vo
where:
Co = Outdoor-air CO2 concentration, standard cubic feet per minute of CO2 per cubic feet per minute of air
Vo = Outdoor-airflow rate, standard cubic feet per minute of air
N = CO2-generation rate, standard cubic feet per minute of CO2 per person
P = Number of people
Ci = Inside CO2 concentration, standard cubic feet per minute of CO2 per cubic feet per minute of air
This simplifies to:
N ÷ (Ci − Co) = Vo ÷ P = R
where:
R = Rate, standard cubic feet per minute of air per person
The model's ability to predict source airflow rate per person is dependent on CO2-production rate, which can vary significantly with activity and age. A typical adult produces 0.0084 scfm of CO2 per met; for office work, the activity level of an adult is approximately 1.2.1 Thus, for an average adult with an activity level associated with office work:
R = 0.010080 ÷ (Ci − Co)
Because CO2 sensors report CO2-concentration levels in parts per million, the equation is more useful written as follows:
R = 10,080 ÷ (Ci* − Co*)
where:
Ci* = Inside CO2 concentration, parts per million
Co* = Outdoor-air CO2 concentration, parts per million
With single-zone systems, a 700-ppm rise in indoor CO2 concentration results in an outdoor-airflow rate of approximately 15 cfm per person. This approximates the minimum ventilation rate established to dilute body odor. Also, it relates to historical references (including ASHRAE Standard 62-1989, Ventilation for Acceptable Indoor Air Quality) to a 700-ppm differential as an indicator of acceptable ventilation.
Because outdoor CO2 level typically hovers around 400 ppm, an indoor CO2 level of 1,100 ppm would suggest the body odor generated in a space would be maintained at acceptable levels.
ANSI/ASHRAE Standard 62.1-2010-Compliant CO2-Based DCV
The ventilation-rate procedure in Section 6 of ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality, has not changed significantly since 2003, when breathing-zone outdoor-air requirements (Section 6.2.2.1) were adjusted to include a floor-area component reflecting the dilution needed for building-related contaminant sources. Today, breathing-zone outdoor-airflow rate, Vbz, is calculated based on table values, as follows:
Vbz = Rp × Pz + Ra × Az
where:
Rp = Outdoor-air rate per person
Pz = Number of persons
Ra = Outdoor-air rate per floor area
Az = Floor area
Traditional fixed-CO2-setpoint DCV. As a result of changes to ANSI/ASHRAE Standard 62.1 in 2003, a fixed CO2 setpoint no longer will result in specified ventilation rates, unless the setpoint is calculated at the lowest expected occupancy (i.e., when ventilation rate is highest).
The relationship between space CO2 level and outdoor-airflow rate per person for a 1,000-sq-ft classroom with a variable occupancy of up to 35 students is illustrated in Figure 2.
The relationship between outdoor airflow and the CO2 level required for compliance with ANSI/ASHRAE Standard 62.1-2010 is a variable and illustrated in Figure 3.
A single CO2 setpoint provides required ventilation for a single population. Excessive population results in a ventilation rate greater than that required by ANSI/ASHRAE Standard 62.1-2010, while deficient population results in a ventilation rate less than that required by ANSI/ASHRAE Standard 62.1-2010. Consider, for example, a CO2 setpoint of 1,000 ppm, which equates to a ventilation rate of approximately 17 cfm per person under the assumptions of steady-state, office-level activity and an outdoor CO2 level of 400 ppm. Figure 4 shows the relationship between ventilation and the requirements of ANSI/ASHRAE Standard 62.1-2010 when a 1,000-ppm CO2 setpoint is maintained. Note that this method will overventilate when population exceeds 15 people and underventilate when population falls below 15 people. Additionally, the CO2 response line will rotate around the origin (0,0) if activity level differs from that assumed. Activity-level variations can affect the outdoor-airflow-intake rate of CO2-based DCV systems significantly (typically, resulting in overventilation). The response also will shift if indoor or outdoor CO2 level is inaccurate.
Want to use this article? Click here for options!
© 2012 Penton Media Inc.
Acceptable Use Policy blog comments powered by Disqus








Recent Comments