Controlling Outside Airflow in VAV Systems

Utilizing mixed-air-plenum pressure to control minimum-outside-air quantity: How to do it and why it works

Page 3 of 5

Article Tools

The return-fan speed is controlled to maintain a constant negative pressure in the mixing box. When commissioning the controls, it is important to know how to select the constant negative-pressure set point in the mixing box to control the return-fan speed. The appropriate set point can be selected by:

  1. Setting up the AHU

    Temporarily set up the unit for 100-percent-outside-air operation: Shut off the return fan, close the return damper, and open the outside-air damper.

  2. Positioning the outside-air damper

    Set the outside-air damper to the selected minimum position. (An arbitrary adjustment, the damper could be anywhere from 10- to 25-percent open.) The minimum position should be high enough to avoid excessive pressure drop, but low enough to leave sufficient stroke for the outside-air dampers to modulate open during the economizer cycle. The example AHU's initial position was 15-percent open (1.5 v on a 0- to 10-v signal to the damper motor).

  3. Making adjustments

    Start the supply fan and adjust the variable-speed drive to deliver the desired minimum outside-air quantity. The example unit had an initial setting of 20-percent speed. If the setting were correct, the desired 4,000 cfm would move at 1,778 fpm in the unit's 18-in.-by-18-in. supply duct.

    The example's measured duct velocity (by pitot traverse) was only 1,000 fpm (2,250 cfm). Pressure in the mixed-air plenum (Point C, Figure 1) was -0.06 in. wg. The airflow was less than the desired minimum, and the mixed-air-plenum pressure was too low to be a workable control set point. After several iterations of increasing fan speed and adjusting outside-air-damper position, a fan speed of 60 percent and a damper position of 25 percent produced a duct velocity of 1,697 fpm (3,818 cfm). The mixed-air-plenum pressure was -0.28 in. wg.

    The minimum outside-air-damper-position set point was left at 25 percent. The mixed-air-plenum-pressure set point was -0.30 in. wg. (The square root of 0.30/0.28 multiplied by the measured 3,818 cfm equals 3,952 cfm, which was acceptably close to the desired 4,000-cfm minimum outside-air quantity.)

  4. Returning the AHU to normal

    Finally, return the unit to normal control. The example AHU's static-pressure profile and airflow measurements were taken at full load and compared with the fan curve as part of the unit's commissioning. The entire process took about 5 to 6 hr.

After the constant negative-pressure set point has been selected and the AHU has been returned to normal control, the relief/spill damper (Damper 1, Figure 1) modulates and tracks the outside-air damper (Damper 3, Figure 1). The relief damper should be closed when the outside-air damper is at minimum.

The return damper (Damper 2, Figure 1) and outside-air damper (Damper 3, Figure 1) are controlled via discharge air or mixed-air temperature as part of the economizer cycle. As the outside-air damper opens beyond minimum, the return damper moves toward a closed position.

Maintaining the minimum outside-air quantity is not the only concern when controlling a VAV unit in a freezing climate. At a full load of 20,000 cfm that included 4,000 cfm of 0°F outside air and 16,000 cfm of 70°F return air, the example AHU's mixed-air temperature was 56°F. Therefore, the mixed-air temperature matched the design supply-air temperature.


Acceptable Use Policy
blog comments powered by Disqus

Social Media

Follow us on

Mike Weil Scott Arnold

Marketplace

Recent Comments

Powered by Disqus
Innovative Solutions

Product Reviews of some of the best new HVACR technology...

Best of 2010!

Best of 2010!


Here are HPAC Engineering's top articles of 2010.
Click here to see if your favorites made the list!

Back to Top

Browse Back Issues

January 2012

December 2011

November 2011

October 2011

September 2011

August 2011