    HVAC and Electric Motors 1

    A multistory commercial office building has a relatively new 1.5-ton split system that cools the elevator equipment room. When the building’s maintenance staff discovered the system was not running and the temperature in the equipment room was abnormally high, an A/C service tech was dispatched. The service tech was unable to find any malfunction in the equipment, but when he measured the voltage on the single-phase circuit serving the condenser and air-handler units, it was 197 with no major loads....More