Make It Work!

While working for a contractor overseas about 25 years ago, I often was required to manage construction projects at remote locations. Considering the time it generally took prefabricated and preassembled systems to arrive on-site, this often necessitated on-site fabrication of tees for piping systems with welded joints.

Article Tools

Straight lengths of pipes of different diameters usually were never in short supply at a project site. However, fittings with specific-size tees for different combinations of pipe diameters usually were. In those instances, engineering basics came to the rescue.

The only information needed to field-fabricate a tee connection was the outer diameter of the pipes to be connected — for example, 6 in. by 3 in. I then used a drafting technique called “development of surfaces,” which involved developing a near-exact curve/profile, such as what one would expect to see on the surface of a 6-in. pipe connected to a 3-in. pipe. I also developed another curve/profile that represented the curvature on the end of the 3-in. pipe when connected to the surface of the 6-in. pipe. These two developed surfaces then constituted the “set” for preparation of a 6-in.-by-3-in. tee (figures 1, 2, and 3).

FIGURE 1. Profiles of 6-in. and 3-in. pipes.

FIGURE 2. Wraparound for larger pipe.

Once the profiles were developed, I wrapped the 6-in.-diameter developed surface on the 6-in. pipe and marked the profile on the pipe (Figure 2). I did the same with the 3-in.-diameter developed surface (Figure 3). The pipes then were cut as per the marked contour. The cut edges were ground for a proper finish/fit, which is similar to how surfaces are prepared for welding.

FIGURE 3. Wraparound for smaller pipe.

Once I prepared the contour sheet sets for the various pipe combinations, field-fabricating the tees was effective and no different than putting together a routine welded pipe joint. This technique proved to be particularly cost-effective for large-diameter (greater than 2 in.) pipes.
Asif Kadiani, PE, CEM, LEED AP
Hanson Professional Services Inc.
Springfield, Ill.

Have a “war story” to share? Send it to Executive Editor Scott Arnold at scott.arnold@penton.com.


Acceptable Use Policy
blog comments powered by Disqus

Follow us on

Mike Weil Scott Arnold

HPAC Engineering eNewsletters

Marketplace

Recent Comments

Powered by Disqus
Innovative Solutions

Product Reviews of some of the best new HVACR technology...

Best of 2011!


Here are HPAC Engineering's top articles of 2011.
Click here to see if your favorites made the list!

Back to Top

Browse Back Issues

May 20121

April 2012

March 2012

February 2012

January 2012

December 2011