Latest from Piping / Pumping

Hpac 1609 Promoscreen Shot 2016 06 29 110745 Am Copy

Data Center Cooling Innovation Delivers Energy Efficiency and Saves Water

June 30, 2016
You can achieve higher levels of energy efficiency and water savings with new data center cooling technology being deployed by Digital Realty and Emerson Network Power. Digital Reality is utilizing Emerson’s pumped refrigerant economization technology throughout its data centers to maximize free cooling throughout the year for lower energy costs and to save more than 300 million gallons of water annually.

A type of cooling economization recently introduced for use in California data centers has proven substantial energy and water savings, two objectives important to data center managers virtually everywhere.  The technology, called pumped refrigerant economization, was accepted for use in data centers by the California Energy Commission (CEC) after an extensive engineering study supported by Digital Realty and Emerson Network Power.
 
The study demonstrated energy and water savings in 14 of the 16 California climate zones, compared to water economization. As a result, CEC now allows pumped refrigerant economization as a prescribed option for data center cooling, in addition to air and water economization.
 
Key results of the engineering study* are as follows:
 
12.8% reduction in MWh of energy used

8.5% reduction in TDV (Time Dependent Valuation (TDV) is a measure of efficiency used by the CEC)

4.339 million gallons of water saved annually, compared to water-side economization

* Based on a 1.2MW data center with standard redundancy assumptions (N+2) and conservative return air temperatures (80°F) with containment, across all 16 California climate zone.

Read the case study describing the initiative.