Energy-Saving Opportunities in Green Buildings

All buildings — even high-performing ones — have room for efficiency improvements

Page 2 of 2

One Pacific Square

Article Tools

A 14-story, 240,338-sq-ft Class A office tower in downtown Portland, Ore., One Pacific Square was acquired by Ashforth Pacific Inc. in August 2006. In 2007, the building received its first Energy Star certification. In 2008, it placed second in BOMA (Building Owners and Managers Association) Portland's Office Energy Showdown.

But Ashforth Pacific did not stop there. Through a one-week energy assessment, the company gained new insight into how the building actually was performing, uncovering an additional $27,700 in annual energy savings.

Because Ashforth Pacific had invested in modern control systems and energy-efficient mechanical systems, the savings came through low- and no-cost measures, such as:

  • Adjusting the temperature setback to remove an unnecessary system override.
  • Lowering the heating set point by 2°F, from 72°F to 70°F.
  • Cutting back the lighting schedule by 1 hr to better match tenant schedules and shutting off lights in a particular area of the building at night.
  • Installation of a demand-controlled ventilation system to more closely match the amount of outside air to building occupancy.

Westmoor Technology Park

Managed by CB Richard Ellis, Westmoor Technology Park in Westminster, Colo., consists of 10 buildings, nine of which meet LEED-EB requirements for minimum energy-efficiency performance. The Energy and Sustainability team within CB Richard Ellis' Technical Services group selected one of the buildings for an American Society of Heating, Refrigerating and Air-Conditioning Engineers Level I energy audit consisting of a building walkthrough and the deployment of an energy-assessment system.

More than $40,000 in annual savings were identified through the following energy-conservation measures:

  • Adjust lighting schedule to better match occupancy.
  • Reduce heating set point and raise cooling set point by 2°F.
  • Reduce overventilation.
  • Add variable-frequency drives to air handlers.
  • Take advantage of daylighting to eliminate lighting in lobby atrium.
  • Adjust HVAC schedule to remove Sunday operation.

Over the first six months of 2009, energy expenditures were more than $7,000 less than they were over the same period in 2008. Even more savings were expected during the warmer summer months.

CONCLUSION

Opportunities to save energy can be found in all buildings, even those that are performing well. The necessary ingredients are:

  • A motivated owner.
  • An operations staff incentivized to save energy.
  • Tools that increase the visibility of energy performance and potential savings.

While significant investments in energy efficiency are justified for some buildings, most “green” buildings already have systems and equipment capable of delivering high energy performance. It is more a matter of making the buildings run better.

Start by benchmarking the energy performance of a building. Conduct a simple energy audit to identify opportunities to save. Most importantly, follow through on corrective actions — particularly simple changes to building operations that will result in immediate savings.

REFERENCE

  1. Turner, C., & Frankel, M. (2008). Energy performance of leed for new construction buildings. Vancouver, WA: New Buildings Institute. Available at http://www.newbuildings.org/downloads/Energy_Performance_of_LEED-NC_Buildings-Final_3-4-08b.pdf

For past HPAC Engineering feature articles, visit www.hpac.com.


The vice president of market development for AirAdvice Inc., a provider of technologies for monitoring and assessing building energy performance, Tim Kensok has 20 years of experience related to HVAC markets, applications, and systems; indoor-air quality; building science; indoor environmental controls; and product development.

LEED-NC Is From Mars, LEED-EB Is From Venus

In 2009, the Energy & Atmosphere (EA) categories of the U.S. Green Building Council's (USGBC's) Leadership in Energy and Environmental Design (LEED) for New Construction and Major Renovations (LEED-NC) and LEED for Existing Buildings: Operations & Maintenance (LEED-EB) green-building rating systems became much more closely aligned. Both systems require a minimum level of energy (LEED-NC) or energy-efficiency (LEED-EB) performance (Prerequisite 2), and both offer additional points for optimizing energy or energy-efficiency performance (Credit 1).

However, the issue of modeled vs. actual energy performance, which can vary by as much as ±50 percent, is difficult to overcome, with the possibility of buildings becoming LEED-NC-certified on the basis of models that predict a much higher level of performance relative to ANSI/ASHRAE/IESNA Standard 90.1-2007, Energy Standard for Buildings Except Low-Rise Residential Buildings, than actually is delivered. One possible solution is to require a year of actual energy-consumption data.


Acceptable Use Policy
blog comments powered by Disqus

Social Media

Follow us on

Mike Weil Scott Arnold

Marketplace

Recent Comments

Powered by Disqus
Innovative Solutions

Product Reviews of some of the best new HVACR technology...

Best of 2010!

Best of 2010!


Here are HPAC Engineering's top articles of 2010.
Click here to see if your favorites made the list!

Back to Top

Browse Back Issues

January 2012

December 2011

November 2011

October 2011

September 2011

August 2011